CL407 Clamp-On Power Data Logger

AEMC CL407 Data Logger

Product Overview
  • 1000V CAT IV Rated
  • UL 94 flame retardant self-extinguishing
  • Agency approvals by UL, CSA, VDE, GS (TUV) (pending)
  • IP54 Rated
  • 10,000 count blue electroluminescent backlit display
  • Measures up to 1000Vac (1400V peak), 1000Vdc and AC+DC with resolution to 10mV
  • Measures up to 1000Aac and 1500Adc
  • Measures single- and three- phase power (Real, Reactive and Apparent) up to 3MW with resolution to 1W
  • Measures Voltage Frequency at 20kHz, Current Frequency 2kHz
  • Auto selects AC or DC measurement
  • True InRush™ current measurement with 1mS capture
  • Measures harmonics up to the 25th
  • Records up to 1000 measurements
  • Bluetooth communication
  • DataView® compatible
  • Jaw opening up to 1.89" (400 series) and up to 2.36" (600 series)
  • Leads are constructed with a flexible silicone material
Useful Links
AEMC CL407 Clamp-On Power Meter Data Logger


Manufacturer - AEMC

Model Number - CL407

Product Spec Sheet

The TRMS Power Clamp-on Data Logger Model 407 provides a new standard for safety and measurement capability not available in any other clamp meter sold today. Safety Rated at 1000V CAT IV, it is safe to operate in all electrical environments. It is rugged enough for the most demanding work environments and will withstand both dust and water spray with its IP54 rating. Ergonomically designed and easily used by one hand, including function selection and button pushing even with a glove on.

In addition to the standard measurement of volts, amps, frequency, resistance, diode checking and continuity, the Model 407 offers several unequaled functions including: AC, DC and AC+DC volts, amps and power, True InRush™, Power measurements, Harmonic analysis, Data logging and more.

CL407 Specifications
Current AC(ms) 1000A
Current DC 1500A
Current AC+DC 1500A Peak
Voltage AC (rms) 1000V
Voltage DC 1000V
Voltage AC+DC 1000V
Ohms 100k Ohms
Continuity (Buzzer) Yes (< 40 Ohms)
Diode Test
Total Harmonic Distortion Yes
Individual Harmonics (to 25th) Yes
Single- and 3-Phase
Real Power (AC, DC, AC/DC)*
1000kW
3000kW
Single- and 3-Phase
Reactive Power (AC, DC, AC/DC)*
1000kvar
3000kvar
Single- and 3-Phase
Apparent Power (AC, DC, AC/DC)*
1000kVA
3000kVA
Temperature (int., ext., C°, F°)
Voltage Frequency (Hz) 20kHz
Current Frequency (Hz) 2kHz
Power Function Yes
THD-r/THD-f Yes
Adapter (AC/DC)
Phase Rotation
Auto AC/DC Yes (V & A)
Auto Power OFF Yes
Hold Button Yes
Backlight Button Yes
Min/Max Button Yes
True InRush™ Function Yes
Relative Function -
Peak ± Function Yes
Harmonics Function Yes
Rec (Record) Function Yes
Wireless BT (Bluetooth) Function Yes
Record (Recordings) 1000
Hz Button Yes
Jaw Opening Size (diameter) 1.89"
Protection Index Housing: IP54 (per standard IEC-60529)/Jaws: IP40

Click image to enlarge

Data Analysis and Reporting Software for Data Loggers

Configure all data logger functions

  • Display and analyze real-time data on your PC
  • Configure all data logger functions and parameters from your PC including sample rate, recording length, channel configuration and more
  • Create and store a complete library of configurations that can be uploaded to the logger as needed
  • Zoom in and out and pan through sections of the graph to analyze the data
  • Download, display and analyze recorded data
  • Display waveforms, trend graphs, harmonics (AC models) and text summaries
  • Create custom views and reports
  • Print reports using standard or custom templates you design




Click image to enlarge
Basic information such as Auto Power Off, instrument name and location, display brightness and contrast (Model PEL 103), setting of the real-time clock and SD card formatting can all be set through the General tab.




Click image to enlarge
The Communication tab provides information about the various communication mediums supported by the instrument with clear and easy setup of all functions from one dialog box.




Click image to enlarge
The Measurement tab specifies the electrical distribution system, voltage ratios, nominal frequency and current probe options and ratios.




Click image to enlarge
In the Recording tab, configure the instrument to measure (and record) over a user selectable recording period from a few hours to a month or longer. Select demand intervals from one to sixty minutes and view available memory for data storage.




Click image to enlarge
Reports can be displayed on a PC and printed. Each report includes all test results in tab and graph format, as well as operator test site information. Comments typed by the operator will also be included.




Click image to enlarge
In the control panel you will find all the necessary tools and selection buttons to review recorded data as trend plots or tabular lists. Also logger selection, when multiple loggers are detected, is accomplished in the control panel.

Request Pricing & Information

If you need information right away or prefer to speak with a person, call us and one of our Experienced Applications Engineers will be happy to talk with you. You can reach us at 1-800-956-4437 during our normal business hours Monday - Thursday from 8am to 5:30pm and Friday 8am to 4:30 pm (EST).

After filling out the form below, an applications engineer will contact you within at least one business day. Fields that are not required are recommended to be filled out so that we can better assist you.

Request Form

Submit the product or application you are interested in and we'll contact you. Need immediate information? Give us a call at 800-956-4437.

Name (required):
Email (required):
Company:
Phone #:
City:
State:
Country:
Product(s) of Interest:
Application:
Additional Information:
Human Verification What is the next number after 9?  

**Your contact information allows us to provide you with pricing information. We never sell or distribute your information. See our Policies page for more information.


Follow CAS Dataloggers on Facebook Follow us on LinkedIn Follow us on Twitter Find us on Google+ Find us on Youtube
Home | About CAS | Policies | Distributor Login | Systems Integrators

©2013 Computer Aided Solutions, LLC.