AEMC Powerpad III 8333

  • Measures TRMS Voltage up to 1000 Vrms AC or 1200 VDC for 1, 2 and 3-phase Systems
  • Measures TRMS Current up to 10 kArms (Sensor Dependent)
  • (4) Voltage Inputs and (3) Current Inputs
  • VA, var, W, kVAh, VARh, kWh and Totals (per Phase) Measurements and Recordings
  • Stores Trend Data, 4,000 Alarms, 51 Captured Transients and up to 12 Screen Snap Shots
  • Measures Harmonics for Voltage, Current or Power up to the 50th Harmonic
  • CE, Shock Resistant and Classified: IEC61000-4-30 Class B, IP50, 1000 V CAT III and 600 V CAT IV
  • USB Communication Interface
  • LCD Display Shows Real-time Waveforms and Trend Data
  • Free DataView software included

Call for configuration and price. 1-800-956-4437

Description

Powerpad III 8333 Three Phase Power Quality Analyzer

The AEMC Powerpad III 8333 Three Phase Power Quality Analyzer is an easy-to-use, compact and shock resistant three-phase power quality analyzer. It enables technicians and engineers to measure and carry out diagnostics and power quality work on single- or three-phase networks. Three current and four voltage input terminals are provided are provided. It is IEC 61000-4-30 Class B and safety rated to 600V CAT IV.

Model 8333 has memory available for storing trend data, alarms, transients, and snapshot data. Capable of storing up to 12 screen snapshots, up to 51 captured transients that contain four cycles for each active input, and 4,000 alarm events from up to 10 different parameters. Trend data can also be recorded for days, weeks or even months.

AEMC 8336 Power Quality Analyzer Kit

Kit includes three MN193 current probes, four black 10 ft voltage leads, four black alligator clips, twelve color-coded input ID markers, NiMH battery, 110/240V power adapter with USB stick supplied with product user manual and DataView software.

Applications include:

  • Verification of power distribution circuits
  • In-plant troubleshooting of power distribution panels and individual machinery
  • Monitor pad mount transformers and phase unbalances
  • Determine harmonic problems originating from source or load
  • Determine transformer K-Factor

Specifications

Input Terminals (4) Voltage
(3) Current
Inputs (3) Voltage
(3) Current
Voltage TRMS (AC+DC): 2 to 1000 Volts
Ratio: Up to 500kV
Current
(TRMS AC+DC)
MN93 Clamp: 500mA to 200Amps AC
MN193 Clamp: 0.005 to 100 Amps AC
SR193 Clamp: 1 Amp to 1000 Amps AC
AmpFlex or MA193 Clamp: 100mA to 10,000Amps AC
MR193 Clamp: 1 Amp to 1300Amps AC/DC
SL261 Clamp: 50mA to 100Amps AC/DC
Ratio: Up to 60kA
Frequency 40Hz to 69Hz
Distribution Systems 1P 2W, 1P 3W, 2P 2W, 2P 3W, 2P 4W, 3P 3W, 3P 4W and 3P 5
W, 2 1/2 Element & Aron Meters
Power Values W, VA, var, VAD, PF, DPF, cos φ, tan φ
Energy Values Wh, VARh, VAh, VADh
Harmonics 1st to 50th Direction, Sequence
THD: 0 to 50, phase
Transients up to 51
Flicker (Pst) Yes
Unbalance Yes
Recording Yes
Alarm Mode 10 types, 4000 Recorded
Peak Yes
Phasor Display Automatic
Display Type: Color 1/4 VGA TFT Screen
Dimensions: 320 x 240, 148mm (Diagonal)
Snapshots 12
Power Supply 9.6 Volt NiMH Rechargeable Battery Pack (Included)
External AC Supply: 110/230 Volts AC ±10% (50/60 Hz)
Battery Life > 13 Hours; 25 Hours (Record Mode)
Communications USB
Languages Supports more than 27
Software DataView (Included)
OS Compatibility Windows 8, 7, Vista, and XP (32-bit and 64-bit)
Standards Compliance CE, IP50, IEC61010-4-30, 1000 V CAT III, 600 V CAT IV
Weight 1.95 kgrams (4.3 lbs)
Dimensions 24.0cm x 18.0cm x 5.5cm (9.8″ x 7.8″ x 2.6″)