The dataTaker DT80 is an intelligent data logger that provides an extensive array of features that allow it to be used across a wide variety of applications. The DT80 is a robust, stand alone, low power data logger featuring USB memory stick support, 18 bit resolution, extensive communications capabilities and built-in display. The dataTaker DT80’s Dual Channel concept allows up to 10 isolated or 15 common referenced analog inputs to be used in many combinations.
Versatile Communication
With support for multiple SDI-12 sensor networks, Modbus for SCADA systems, FTP and Web interface, 12V regulated output to power sensors, the DT80 is ready to be rolled out into environmental, industrial and many other types of monitoring projects.
Communications features include RS232 with modem support, USB, Ethernet and USB memory stick ports. Connect to the DT80 locally, remotely or over the Internet. The web interface allows users to configure the DT80, access logged data and see current measurements as mimics or in a list using a web browser. FTP provides data to your office over the internet or mobile phone network, without the need for polling or specific host software.
Universal & Configurable
Analog and digital channels, high-speed counter inputs, phase encoder inputs and programmable serial sensor channels allow the DT80 to easily connect to most sensors and data measurement sources. Temperature, voltage, current, 4-20mA loops, resistance, bridges, strain gauges, frequency, digital, serial and calculated measurements can all be scaled, logged and returned in engineering units or within statistical reporting. Group sampling, logging, alarm and control tasks within schedules to suit your requirements. Smart sensors, GPS, PLCs and other intelligent devices are supported via 2 serial sensor ports (RS232 or RS422/485), with our optional CANgate interface available for CAN bus applications.
Easy Data Management
Store up to 10 million data points in user defined memory, log as much or as little as you need with independent control of schedule size and mode. Overwrite or stop logging once allocated memory is full. Archive data on alarm event, copy to USB memory or transfer via FTP, the choice is yours.
dEX Software
dEX is an intuitive graphical interface that allows you to configure your data logger, view real-time data in mimics, trend charts or tables and retrieve your historical data for analysis.
dEX runs directly from your web browser and can be accessed either locally or remotely, anywhere that a TCP/IP connection is available including worldwide over the Internet. You can use any of the logger’s built-in communications ports to view dEX including Ethernet, USB and RS-232.
- Built-in software - no application to install
- Runs directly from your web browser
- Accessible by Ethernet or USB connection
- Intuitive graphical interface
- Easy-to-use configuration editor
- Access live and historical data
- View data charts, mimics and tables
Real Time Trending
Real-time trending for sensors, calculations or other data. Supports up-to 5 traces per chart and up-to 2 Y-axes. Backfills with historical data stored in logger.
Real Time Displays
dEX displays real-time sensor measurements, calculations and diagnostic information, including mimics, tables and trend charts
Configuration Made Easy
The configuration editor allows you to view, edit and save logger configurations in an easy-to-use Windows Explorer style user interface. Tree view of configuration allows definition of measurement schedules and measurements.
Wiring diagrams show possible wiring configuration for selected sensor type. Configuration can be stored and retrieved on either the logger or a local computer

|
|
20 Channel Expansion Module CEM20A dataTaker CEM20 connects to one analogue channel of the dataTaker data logger. Each CEM20 connects 20 universal data logging channels.
|
|
|
CANgate CANbus to Serial ConverterThe dataTaker CANgate CAN to ASCII gateway filters and converts CAN (Controller Area Network) and GPS (Global Positioning System) data to serial ASCII data.
|
|
|
Portable Enclosure
|
|
|
Industrial Enclosure
|
| Analog Channels | |
|---|---|
| Analog Channels |
2 Wire w/ Com. Ref. Terminal: 15 Channels (expandable to 300*) 2 Wire Isolated: 10 Channels (expandable to 200*) 3 or 4 Wire Isolated: 5 Channels (expandable to 100*) * Expansion requires optional CEM20 |
| Analog Inputs |
Inter-Channel Isolation: 100 Volts (Relay Switching) Analog Section Isolation: 100 Volts (Opto-Isolated) Input Impedance: 100 KO, >100MO Common Mode Range: ±3.5V or ±35V on 30 Volts Range |
| Analog Measurement Ranges |
Voltage: ±30 mVdc; ±300 mVdc; ±3 Vdc; ±30 Vdc Current: ±0.3 mA; ±3 mA; ±30 mA Resistance: 100O; 1,000O; 10,000O Frequency: 100Hz; 10 kHz |
| Analog Measurement Resolution |
Voltage: 0.25µV; 2.5µV; 0.25µV; 250µV Current: 2.5nA; 25 nA ; 250 nA Resistance: 1.5 mO; 15 mO; 150 mO Frequency: 0.0002%; 0.0002% |
| Accuracy |
DC Voltage: 0.1% (5°C to 40°C); 0.35% (-45°C to 70°C) DC Current: 0.15% (5°C to 40°C); 0.45% (-45°C to 70°C) DC Resistance: 0.1% (5°C to 40°C); 0.35% (-45°C to 70°C) Frequency: 0.1% (5°C to 40°C); 0.25% (-45°C to 70°C) |
| Sampling |
Integrates over 50/60 Hz Line Period for Accuracy and Noise Rejection Maximum Sample Speed: 25 Hz Effective Resolution: 18 Bits Linearity: 0.01% Common Mode Rejection: >90dB Line Series Mode Rejection: > 35dB |
| Sensor Excitation (Supply) |
Analog Channles: Selectable 250µA or 2.5mA Precision Current Source, 4.5V Voltage Source, or Switched External Supply General Purpose: Switchable 12V Regulated Supply for Powering Sensors & Accessories (Max. 150mA) |
| Analog Sensors | |
|---|---|
| Thermocouples |
Type: B, C, D, E, G, J, K, N, R S, T Calibration Standard: ITS-90 |
| RTDs |
Materials Supported: Pt, Ni, Cu Resistance Range: 10O to 10KO |
| Thermistors |
Type: YSI 400xx Series, other Types* Resistance Range: <10kO** * Other Thermistor Types are Supported by Thermistor Scaling and Calculated Channels ** Resistance Range Can Be Increased with the Use of a Parallel Resistor. |
| Monolithic Temperature Sensors | Type: LM34 - 60, AD590, AD592, TMPxx, LM135, LM235, LM335 |
| Strain Gauge and Bridge Sensors |
Configurations: 1/4, 1/2 & Full Bridge Excitation: Voltage or Current |
| 4-20mA Current Loop | Internal 100R Shunt or External Shunt Resistor |
| Digital Channels | |
|---|---|
| Digital Input/Outputs |
8 Bi-Directional Channels Digital Input Type: 8 Logic Level (Max. 20/30 Volts) Digital Output Type: 4 With Open Drain FET (Max. 30V, 100mA), 4 with Logic Output |
| Relay Output | 1 Latching Relay, contacts (Max: 30Vdc, 1A) |
| Counter Channels | |
|---|---|
| Low Speed Counters |
-- 8 Counters Shared with Digital Inputs -- 32 Bit Size -- 10 Hz Max Count Rate -- Low Speed Counters do not Function in Sleep Mode |
| Dedicated Counter Channels |
-- 4 High Speed Inputs or 2 phase encoder (quadrature inputs) -- 32 Bit Size -- 100kHz Max Count Rate -- 2 Logic Level Inputs (Max ±30V) -- 2 Sensitive Inputs (10mV) for Magnetic Pick Ups (Max. ±10V) |
| Serial Channels | |
|---|---|
| SDI-12 |
-- 4 SDI-12 Inputs, Shared with Digital Channels -- Each input can support multiple SDI-12 Sensors |
| Generic Serial Sensor |
Flexible Option for Logging From Wide Range of Smart Sensors and Data Streams Available ports: Serial Sensor Port (RS232, RS422, RS485) or Host RS232 Port* Baud Rate: 300 to 115,200 * If used as a Serial Sensor channel then the Host Port is Not Available for Other Communications |
| Calculated Channels | |
|---|---|
| General | Combine values from analog, digital and serial sensors using expressions involving variables and functions. |
| Functions | Arithmetic, Trigonometric, Relational, Logical and Statistical |
| Alarms | |
|---|---|
| Condition | High, Low or Within Range and Outside Range |
| Delay | Optional Time Period for Alarm Response |
| Actions | Set Digital Outputs, Transmit Message, Execute any DataTaker Command |
| Scheduling of Data Acquisition | |
|---|---|
| Condition | High, Low or Within Range and Outside Range |
| Number of schedules | 11 |
| Schedule rates | 10ms to days |
| Internal Data Storage | Capacity: 128mb = approx 10,000,000 data points |
| Removable USB storage device |
Type:compatible with USb 1.1 or USB 2.0 drivers, e.g. Flash drive Capacity: approx 90,000 data points per megabyte |
| Communication Interfaces | |
|---|---|
| Ethernet Port |
Interface: 10BasteT (10Mbps) Protocol: TCP/IP |
| USB Port |
Interface: USB 1.1 (virtual COM port) Protocol: ASCII command |
| Host RS232 Port |
Speed: 300 to 115,200 Baud (57,600 Default) Flow Control: Hardware (RTS/CTS), Software (XON/XOFF), None Handshake Lines: DCD, DSR, DTR, RTS, CTS Modem Support: Auto-Answer and Dial Out Protocols: ASCII Command, TCP/IP (PPP), Serial Sensor, Modbus |
| Serial Sensor Port |
Interface: RS232, RS422m, RS485 Speed: 300 to 57,600 baud Flow Control: Hardware (RTS/CTS) Software: (XON/XOFF), None Protocols: Modbus (master & slave), Serial Sensor |
| Network TCP/IP Services | |
|---|---|
| Network | Ethernet and/or Host RS232 (PPP) Communication Ports |
| Command Interface | Access the ASCII command interface via TCP/IP |
| Web Server |
-- Access Current Data and Status from any Web Browser -- Download Data in CSV Format -- Command Interface Window -- Define Mimic Displays |
| Modbus Server(slave) | Access current data and status from any Modbus client |
| FTP Server | Access logged data from any FTP client or web browser |
| FTP Client | Automatically upload logged data direct to an FTP server. |
| System | |
|---|---|
| Display and Keypad |
Type: LCD, 2 Line by 16 Characters, Backlight Functions: Channel Data, Alarms, System Status Keypad: 6 Keys for Scrolling and Function Execution Status LEDs: 4 (Sample, Disk, Attention, Power) |
| Firmware Upgrade | Via: RS232, Ethernet, USB disk. |
| Real Time Clock |
Normal resolution: 200µs Accuracy: ±1 min/year (0°C to 40°C), ±4 min/year (-40°C to 70°C) |
| Power Supply |
External Voltage Range: 10 to 30 Volts DC Internal battery: 6Vdc 1.2Ahr lead acid Peak Power: 12 W (12VDC 1A) |
| Average power Consumption |
Using 12Vdc external power source 1 Sec Sampling: 1350 mW 5 Sec Sampling: 500 mW 30 Sec Sampling: 135 mW 5 Min Sampling: 70 mW 1 Hr Sampling: 60 mW |
| Typical Operating Time |
from internal 6Vdc, 1.2Ahr battery
1 Sec Sampling: 6.5 hours 5 Sec Sampling: 1 day 1 Min Sampling: 10 days 1 Hr Sampling: 3.5 months |
| Physical Environment | |
|---|---|
| Construction | Powder Coated Steel & Anodized Aluminum |
| Dimensions | 180 x 137 x 65mm |
| Weight | 1.5kg (4kg shipping) |
| Operating Range |
Temperature: -45°C to 70°C (Reduced LCD Operation Outside Range: -15°C to 50°C) Humidity: 85% RH, Non-condensing |
Application Notes
Below features our collection of application notes and case studies involving this product.
Power Metering with a DT80 Using WattNode Transducers
Data Monitoring for a Rural Development Charity
Monitoring Solar Hot Water Systems
Testing Filtration Systems in Pools and Hot Tubs
Vehicle Data Acquisition For Component Reliability Testing
Knowing the Strength of Curing Concrete
Monitoring Two Plants with Simultaneous Data Sharing
Temperature and Sterilization Monitoring in a Rice Mill
Monitoring Exported Perishables Throughout Shipping
Dashboards Efficiently Monitor Utility Usage in a School Building
The World's Fastest DT80
Testing Fuel Consumption in a Gold Mine
Request Pricing & Information
If you need information right away or prefer to speak with a person, call us and one of our Experienced Applications Engineers will be happy to talk with you. You can reach us at 1-800-956-4437 during our normal business hours Monday - Friday from 8am to 6pm (EDT).
After filling out the form below, an applications engineer will contact you within at least one business day.
* Indicates a required field.
Fields that are not required are recommended to be filled out so that we can better assist you.