  • Monitors and displays CO2, temperature and humidity
  • Stores up to 1 million measurements
  • Multiple display modes for easy data viewing
  • Adjustable alarm settings
  • Multiple mounting options (Magnetic, Wall Bracket, Desk Top Stand or Strap)
  • Start and stop data recording, store results in logger
  • USB and Bluetooth communication for downloading recorded data
  • Data analysis software included for viewing real-time data, configuring and running recording sessions, downloading recorded data, and creating AQR reports

$495.00

Description

CA 1510 Indoor Air Quality Data Logger

Indoor air quality has become a significant public health concern in recent years. The AEMC CA 1510 Indoor Air Quality Data Logger helps address this issue by monitoring temperature, humidity, and carbon dioxide (CO2) in the local environment. This compact, easy-to-use instrument provides quick and accurate readings and can store up to a million measurements.

Monitoring CO2 levels in these environments can be highly beneficial. In addition to the potential health effects caused by breathing high concentrations of this gas, the CO2 level also serves as a good indicator of the efficiency of the building’s air ventilation and circulation system.

Free Android app:

You can also work with the C.A 1510 from an AndroidTM mobile device by downloading a free app from the Google Play Store. The app enables you to connect to the instrument, view measurement data (in tabular or graphical format), start and stop a recording session, download recorded data, configure the instrument, and perform other tasks.

Applications include:
  • Schools
  • Workplaces (office and factory)
  • Hospitals
  • Government and other public buildings
  • Airports, Train and Bus Stations
  • Private residences

Specifications

CO2 Measurement
Measuring PrincipleNon-dispersive infrared (NDIR) technology
Type of SensorDouble-bean infrared cell sensor
Measurement Range0 to 5000 ppm
Accuracy±50ppm ±3% of value measured
Response time to 63%
Resolution1 ppm
Temperature Measurement
Type of SensorCMOS
Units°F or °C
Measurement Range14° to +140°F (-10° to +60°C)
Accuracy±0.9°F (0.5°C)
Resolution0.1°F (0.1°C)
Humidity Measurement
Type of SensorCapacitive
Measurement Range5 to 95% RH
Accuracy±2% RH
Resolution0.1% RH
General
Recording IntervalProgrammable from 1 minute to 2 hours
StorageUp to 1 million measurements
AlarmYes
Backlighting, Display Hold Function & Min-MaxYes
Automatic Power-OffYes (in portable mode only)
Operating RangeTemp: 14° to +140°F (-10° to +60°C)
Humidity: 5 to 95% RH
Dimensions4.92 x 2.58 x 1.26″ (125 x 65.5 x 32)
Weight6.70 oz (190g with batteries)
ProtectionIP40
ComplianceIEC 61010-1, 50V CAT II – IEC 61326-1
Power SupplyAlkaline batteries; 2AA or rechargeable battery connection to 120V 60Hz line / USB to wall adapter
CommunicationBluetooth Class 2 wireless communication USB link
MountingEmbedded magnets on backside, tear drop wall hook, optional padlockable wall mount (padlock not included)
Functions of the AQR (Air Quality Report) software, for PC, supplied with modelGraphic representation or as table of values, data export, real-time mode calculation of the confinement index with selection of presence periods & report generation