AEMC Powerpad III 8336

  • Measurement of TRMS voltages up to 1000Vrms AC/DC for two-, three-, four- or five-wire systems
  • Measurement of TRMS currents up to 10,000Arms (sensor dependent)
  • Direct measurement of neutral current & voltage
  • Frequency measurement (40 to 69Hz)
  • Record and display trend data as fast as once per second for one month for up to 41 variables
  • Transient detection on all V and I inputs (up to 210)
  • Measures harmonics for voltage, current or power up to the 50th harmonic
  • Recording, time stamping and characterization of disturbance
  • 2GB SD Card for Trend Recording memory; Alarm, Snapshot, Transient and Inrush stored in internal flash memory
  • 65µs/sample trend recording
  • Includes free DataView® software for configuring data storage, real-time display, analysis and report generation

Call for configuration and price. 1-800-956-4437

Description

AEMC 8336 Power Quality Analyzer KitThe Powerpad III 8336 Three Phase Power Quality Analyzer from AEMC is an easy-to-use, compact and shock resistant data logger kit. Technicians and engineers can measure and carry out diagnostics and power quality work on one-, two- or three-phase networks. Five voltage and four current inputs are provided. It is IEC 61000-4-30 Class B and safety rated to 600V CAT IV and 1000V CAT III.

The Powerpad III 8336 Three Phase Power Quality Analyzer has 2GB of memory available for storing trend data. Additional internal memory is used to let you store alarms, transients, and snapshot data. Capable of storing up to 50 screen snapshots, up to 210 captured transients that contain four cycles for each active input or inrush data for up to 10 minutes, and 10,000 alarm events from up to 40 different parameters. Trend data can also be recorded for days, weeks or even months. Inrush current can also be captured and stored.

Kit includes:

  • 5 black 10 ft voltage leads
  • 5 black alligator clips
  • 12 color-coded input ID markers
  • USB cable
  • NiMH battery
  • 110/240V power adapter with US power cord
  • Toolbag
  • Soft carry pouch
  • User guide
  • USB stick supplied with product manual and DataView® software

Applications include:

  • Verification of power distribution circuits
  • In-plant troubleshooting of power distribution panels and individual machinery
  • Monitor pad mount transformers and phase unbalances
  • Determine harmonic problems originating from source or load
  • Determine transformer Factor-K
  • Energy metering (kVAh, VARh, kWh)

Specifications

Input Terminals (5) Voltage
(4) Current
Inputs (4) Voltage
(4) Current
Voltage TRMS (AC+DC): 2 to 1000 Volts
Ratio: Up to 500kV
Current
(TRMS AC+DC)
MN93 Clamp: 500mA to 200Amps AC
MN193 Clamp: 0.005 to 100 Amps AC
SR193 Clamp: 1 Amp to 1000 Amps AC
AmpFlex or MA193 Clamp: 100mA to 10,000Amps AC
MR193 Clamp: 1 Amp to 1300Amps AC/DC
SL261 Clamp: 50mA to 100Amps AC/DC
Ratio: Up to 60kA
Data Storage 2 GB card for trend + 4MB aprtitioned for snapshot, transients, alarms
Frequency 40Hz to 70Hz
Distribution Systems 1P 2W, 1P 3W, 2P 2W, 2P 3W, 2P 4W, 3P 3W, 3P 4W and 3P 5W, 2 1/2 Element & Aron Meters
Power Values W, VA, var, VAD, PF, DPF, cos φ, tan φ
Energy Values Wh, VARh, VAh, VADh
Harmonics 1st to 50th Direction, Sequence
THD: 0 to 50, phase
Transients up to 210
Flicker (Pst & Plt) Yes
Inrush Mode Yes > 10 Minutes
Unbalance Yes
Recording Yes
Alarm Mode 40 types; 10,000 Recorded
Peak Yes
Phasor Display Automatic
Display Type: Color 1/4 VGA TFT Screen
Dimensions: 320 x 240, 148mm (Diagonal)
Snapshots 50
Power Supply 9.6 Volt NiMH Rechargeable Battery Pack (Included)
External AC Supply: 110/230 Volts AC ±10% (50/60 Hz)
Battery Life 10 hrs in non-record mode with display on; 25 hrs in record mode display off
Communications USB
Languages Supports more than 26
Software DataView (Included)
Electrical Safety IEC61010, 1000V CAT III / 600V CAT IV
Protection IP53 – Non Operating
Weight 1.95 kgrams (4.3 lbs)
Dimensions 24.0cm x 18.0cm x 5.5cm (9.8″ x 7.8″ x 2.6″)

Displays

8336-powerpad-display-screens